ID200

Heat detector

The response characteristics of the ID200 heat detector have been carefully set in A1R mode (fixed threshold at 58°C with thermovelocimetric detection). However, it can be set (by means of EDRV1000 driver) to operate in B mode (fixed threshold at 72°C); in A2S mode (fixed threshold at 58°C); in BR mode (fixed threshold at 72°C with thermovelocimetric detection).

As a result of such flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.

Black plastic enclosures available.

 